CONNECTION TYPE:
Parallel Connected
AGENCY LISTINGS:
ANSI/UL 1449 Third Edition, UL 1283 (Type 2 locations), cUL (Type 2 locations)
MAXIMUM CONTINUOUS OPERATING VOLTAGE RANGE:
120VAC 125%, all others 115%
MAXIMUM SURGE CURRENT RATING:
65kA-200kA per mode; 130kA-400kA per phase
UL 1449 SHORT CIRCUIT RATING:
200kAIC
UL 1449 LOCATION TYPE:
Type 1, Type 2
NOMINAL DISCHARGE CURRENT (IN):
20kA
OPERATING FREQUENCY RANGE:
47-63 Hz
50 OHM EMI/RFI ATTENUATION:
63dB Max from 10kHz to 100 MHz
PROTECTION MODES:
All applicable modes standard (Line to Neutral, Line to Ground, Neutral to Ground and Line to Line)
MONITORING FEATURES:
Internal/External Status LEDs, Audible Alarm, Summary Alarm Contact, Built-in-test circuit tests MOV/fuse array capacities, Phase loss indication, Low voltage indication, Loss of power indication, Surge counter
(optional)
(optional)
RESPONSE TIME:
<0.5 nanoseconds
TEMPERATURE:
-40 to +60 degrees C
OPERATING HUMIDITY:
0% to 95% non-condensing
STATUS INDICATION:
LEDs, Relay Alarm Contacts, Audible Alarm
ENCLOSURE:
NEMA 4X, 12, 1
ALTITUDE:
0 to 18,000 feet
AUDIBLE NOISE:
Less than 45 dBa
PARTS WARRANTY: